Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T06CM05804
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/19/2008 | MECHANICAL - ABOVE CEILING | Approved | ||
07/31/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING TILES 2ND & 4TH FLOOR CORRIDORS |
|
07/28/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK FOR CEILING TILES 3RD FLOOR CORRIDOR |
|
07/23/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK FOR CEILING TILES 5TH FLOOR CORRIDOR |
|
07/11/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 2ND THRU 5TH FLOOR LOBBIES & VESTIBULES OK FOR CEILING TILES. MARIO @ 240-6403 |
|
06/13/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. A/C 4R HAS NO ACCESS TO ANY SERVICE PANELS 2. PROVIDE SECONDARY CONDENSATE DRAINS 3. RELOCATE DISCONNECTS BLOCKING ACCESS TO A/C 6R 4. TRAPS BUILT BACKWARDS 5. ALLOW PROPER ACCESS TO AIR FILTERS 6. PROVIDE DUCT SMOKE DETECTORS IN ALL UNITS IN A COMMON RETURN AIR PLENUM EXCEEDING 2000 CFM COMBINED AS PER 606.2.2 IMC |
|
02/20/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | 5TH FLOOR RESTROOM OK TO SHEETROCK CEILINGS 1ST FLOOR FIRE DAMPER MOTORS IN SHAFT HAVE NO ACCESS FOR REMOVAL OR SERVICE JIM @ 240-9295 TROY @ 240-4484 |