Permit: T06CM05804

Parcel: 13317064B

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
08/19/2008 MECHANICAL - ABOVE CEILING Approved
07/31/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING TILES 2ND & 4TH FLOOR CORRIDORS
07/28/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK FOR CEILING TILES 3RD FLOOR CORRIDOR
07/23/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK FOR CEILING TILES 5TH FLOOR CORRIDOR
07/11/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
2ND THRU 5TH FLOOR LOBBIES & VESTIBULES OK FOR CEILING TILES.

MARIO @ 240-6403
06/13/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. A/C 4R HAS NO ACCESS TO ANY SERVICE PANELS
2. PROVIDE SECONDARY CONDENSATE DRAINS
3. RELOCATE DISCONNECTS BLOCKING ACCESS TO A/C 6R
4. TRAPS BUILT BACKWARDS
5. ALLOW PROPER ACCESS TO AIR FILTERS
6. PROVIDE DUCT SMOKE DETECTORS IN ALL UNITS IN A COMMON RETURN AIR PLENUM EXCEEDING 2000 CFM COMBINED AS PER 606.2.2 IMC
02/20/2008 MECHANICAL - ABOVE CEILING Partial Approval 5TH FLOOR RESTROOM OK TO SHEETROCK CEILINGS
1ST FLOOR FIRE DAMPER MOTORS IN SHAFT HAVE NO ACCESS FOR REMOVAL OR SERVICE

JIM @ 240-9295
TROY @ 240-4484