Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T06CM05804
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/19/2008 | MECHANICAL - INTERMEDIATE | Approved | ||
05/19/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 433,000 BTU FURNACE 10' FROM REGULATOR REQUIRES MIN. 1" PIPE 3/4" PIPE WAS USED. SEE TABLE 402.4 IFGC |
|
02/08/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SUPPLY & EXHAUST IN COMMON RESTROOMS 4, 3, 2 AND 1 FLOORS. OK TO SHEETROCK CEILINGS |