Permit: T06CM05804

Parcel: 13317064B

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM05804

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/20/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
YOU STILL HAVE OPEN SEWER VENTS ON THE 5TH FLOOR!!!
08/19/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1. STILL HAVE WATER HAMMER NOISE AT 1ST LEVEL FLUSHOMETERS
2. YOU MAY HAVE EXCESSIVE WATER PRESSURE
3. ADJUST BOOSTER PUMP
4. CORRECT CROSS THREADED UNION
5. SEAL WALL PENETRATIONS
08/18/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CALL IN ALL PLUMBING INSPECTIONS THAT HAVE NOT BEEN APPROVED ON THIS SHEET AND INSPECTION CARD
08/15/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
CORRECT WATER HAMMER AT 1ST LEVEL TR. OPEN ALL TRAP PRIMER VALVES
INSTALL STRAINERS AND GRATES IN FS's
SEAL WALL PENETRATIONS SEAL CO PLUGS
08/14/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
TRS 2-5 OK
TR1 CORRECT CRITICAL LEVEL, INSTALL HAMMER ARRESTORS
CORRECT TRAP PRIMER PIPING AT PENTHOUSE
STILL NEED TO INSPECT PENTHOUSE AND COOLING TOWER
PROVIDE STERILIZATION AND BACKFLOW PAPERWORK
INSTALL MISSING PIPE CLAMPS AND CAPS ON OPEN DWV PIPING. EXTERIOR CLEANOUTS.