Permit: T06CM05804

Parcel: 13317064B

Inspection Status: Approved

Inspection History: SITE - SEWER

Permit Number - T06CM05804

Inspection Description - SITE - SEWER

Inspection Status - Approved

Date Description Inspector Results Comments
08/14/2008 SITE - SEWER Approved IVRS - Inspection :*
07/10/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
SEWER TIE-INS OK
07/09/2007 SITE - SEWER Denied IVRS - Inspection :
See detailed listing on site.| 999*
USE APPROVED TRANSITION COUPLINGS
07/02/2007 SITE - SEWER Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSTALL SEDIMENT WELD ADAPTOR BUSHINGS ON SDR OR PROVIDE PRODUCT LISTING FOR TRANSITION COUPLING.
06/26/2007 SITE - SEWER Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL PVC HUB IN CORRECTION DIRECTION OF FLOW
2. SUPPORT PVC AT CONNECTION
3. PROVIDE THIN WALL TO SCH 40 ADAPTORS AT C1 TO PLASTIC TRANSITION.
06/20/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
5 PSI AIR TEST OK
NEED TO SEE BUILDING DRAIN CONNECTIONS AND CLEANOUT TERMINATIONS
06/19/2007 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
06/15/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
1) OK TO COVER ALL SEWER
2) AIR TEST AT LATER TIME
06/14/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
1) 6" SDR FROM CLEANOUT INSIDE PROP 3 LENGTHS INSTALLED
2) OK TO COVER
3) AIR TEST MAN HOLE AT LATER DATE