Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESS TEST FNL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/27/2008 | PLUMBING - GAS PRESS TEST FNL | Approved | IVRS - Inspection :* | |
| 05/22/2008 | PLUMBING - GAS PRESS TEST FNL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GAS REGULATOR PIPING SHALL BE THE SAME MATERIAL SPECIFIED FOR GAS PIPING SPEC 210 2) RED LINE REGULATOR VENT LOCATIONS |
|
| 04/28/2008 | PLUMBING - GAS PRESS TEST FNL | Not ready for Inspection | IVRS - Inspection :* | |
| 04/25/2008 | PLUMBING - GAS PRESS TEST FNL | Not ready for Inspection | IVRS - Inspection :* PROVIDE MINIMUM 60 PSI TEST WITH REDLINE ON SITE CITY APPROVED PLAN TO FOLLOW |