Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T06CM05804
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/16/2008 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* WELDER CERTS OK LOW PSI TEST & HANGERS OK INSTALL REGULATORS RECALL FOR GAS TEST FINAL |
|
05/14/2008 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* LOW PSI TEST AND SUPPORTS PREVIOUSLY NOTED. ALSO, PROVIDE WELDER CERTIFICATION. NEED PLAN REVISIONS, AND ALL EQUIPMENT INSTALLED FOR GAS CLEARANCE. ALSO, NEED MECHANICAL APPROVAL |
|
04/28/2008 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* 60+ PSI TEST ON 4" FROM METER LOCATION TO CAPPED VERTICAL STUBS AT 1" ABOVE ROOF LEVEL AND 3' ABOVE PENTHOUSE FLOOR LEVEL PER REDLINE ON SITE FOR 2 PSI SYSTEM ONLY. PROVIDE TESTING ON INCHES SYSTEM. THIS SYSTEM WILL REQUIRE REVISED CITY APPROVED PLAN. PROVIDE HANGERS AT CHANGES OF DIRECTION AND ELEVATION. |
|
04/25/2008 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* |