Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM05804
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/19/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/23/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CLOSET FLANGES OK FOR LEVEL 2 THRU 5 SOUTHWEST RESTROOMS ONLY |
|
04/21/2008 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
03/13/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* LEVEL 5 DOMESTIC WATER OK TO INSULATE PER YOUR PLAN SPECS HANGERS SHALL BE PER T 3-2 UPC PLUGS SHALL BE BRASS |
|
03/03/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* INSTALLER PER PLUMBING GENERAL REQUIREMENTS 15400 INSULATION |
|
02/27/2008 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* HANGERS STILL MISSING ABV CEILING OF TRS HANGERS STILL MISSING ON HW RECIRC. C1 REQUIRES HANGERS AT EACH END OF EACH RISER CU HANGER SPREAD 6' MAX. ALSO, PROVIDE CLEARANCE AT BUTTERFLY V CONTINUED DENIED INSPECTIONS WILL RESULT IN REFEE |
|
02/26/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DWV WATER TEST TO PENTHOUSE OK INSTALL MISSING HANGERS ON WASTE AND WATER USE CU HANGERS ON COPPER PIPE INSTALL HAMMER ARRESTORS COMPLETE SUPPORTS ON RWL |
|
02/21/2008 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 3X2 RESTRICTION AT FS IMPROPER USE OF FITTINGS AT VENT CONNECTIONS REVENTING BELOW FLOOD LEVEL SUPPORTS MISSING ISOLATION OF COPPER FROM METAL |
|
02/11/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* L 5 TRS TESTING OK; NEED TO SEE PIPE INSULATION ISOLATION FROM METAL AND VENT CONNECTION ALSO, HAMMER ARRESTORS & CLOSET FLANGES |
|
02/06/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* LEVELS 3 & 4 PIPE INSULATION OK SECURE W/CORRECT SIZE CLAMPS INSTALL FHA STRAPS WITHIN 1 1/4 OK TO COVER WALLS IN LEVEL 3 & 4 TOILET RMS |
|
01/29/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - LEVEL 4 DWV & DOM. WATER TEST OK - HAMMER ARRESTORS REQUIRED ON ALL BRANCH PIPING TO FLUSH-O-METERS - BRACE VENTS - INSULATE HW RECALL FOR INSPECTION - SUPPORT WATER PIPING AT LAVS - RISER CLAMPS ON C1 THRU FLOOR - SUPPORTS REQUIRED ON EACH END OF C1 - CALL FOR ROOF DRAIN INSPECTION - 03037 6" RWL AT 1/K TESTED TO ROOF |
|
01/25/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 3RD FLOOR RESTROOMS OK NEED TO SEE PIPE INSULATION WILL INSPECT CLOSET FLANGES AFTER FF |
|
01/22/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RWL IN EAST CHASE W/TEST THRU ROOF OK DWV WEST CHASE W/TEST THRU ROOF OK |
|
01/16/2008 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSTALL SOLID PIPE SUPPORTS ON CAST IRON IN CHASE PIPING WET. POSSIBLE LEAKS. RECALL FOR INSPECTION |
|
01/15/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DWV IN CHASE TO 3RD LEVEL OK DOMESTIC WATER W/90 PSI TEST OK |
|
12/28/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - BRANCH PIPING SERVING DOMESTIC WATER TO 1ST & 2ND LEVEL - TOILET RMS OK TO INSULATE - ALL BRANCH LINES SERVING FLUSH-O-METER VALVES REQUIRE WATER HAMMER ARRESTORS PER UPC SEC 609.10 |
|
11/27/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
11/13/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DOMESTIC WATER PIPING LEVEL 3 EAST OF COL G TEST OK 2) REMOVE ANY EXCESS FLUX PRIOR TO INSULATION. SUPPORTS AT EAST END 3) DOMESTIC WATER SERVICE PIPING OK PROVIDE TEST 4) INSTALL CORRECT SIZE VENT FITTING AT 1ST FLOOR TRS AND RETEST 5) TEST ON WASTE PIPING 1ST AND 2ND LEVEL TO 9' ABV 2ND LEVEL OK |
|
11/01/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WATER PIPING LEVEL 2 OK |
|
10/24/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ROOM #110 WATER TEST OVERHEAD OK FOR WATER PIPING |
|
10/03/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DWV FROM FF TO CEILING OF LEVEL 2 W/TEST |