Permit: T06CM05804

Parcel: 13317064B

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM05804

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/19/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
04/23/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CLOSET FLANGES OK FOR LEVEL 2 THRU 5
SOUTHWEST RESTROOMS ONLY
04/21/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/13/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
LEVEL 5 DOMESTIC WATER
OK TO INSULATE PER YOUR PLAN SPECS
HANGERS SHALL BE PER T 3-2 UPC PLUGS SHALL BE BRASS
03/03/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
INSTALLER PER PLUMBING GENERAL REQUIREMENTS 15400 INSULATION
02/27/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
HANGERS STILL MISSING ABV CEILING OF TRS
HANGERS STILL MISSING ON HW RECIRC.
C1 REQUIRES HANGERS AT EACH END OF EACH RISER
CU HANGER SPREAD 6' MAX.
ALSO, PROVIDE CLEARANCE AT BUTTERFLY V
CONTINUED DENIED INSPECTIONS WILL RESULT IN REFEE
02/26/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV WATER TEST TO PENTHOUSE OK INSTALL MISSING HANGERS ON WASTE AND WATER
USE CU HANGERS ON COPPER PIPE
INSTALL HAMMER ARRESTORS
COMPLETE SUPPORTS ON RWL
02/21/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
3X2 RESTRICTION AT FS
IMPROPER USE OF FITTINGS AT VENT CONNECTIONS
REVENTING BELOW FLOOD LEVEL
SUPPORTS MISSING
ISOLATION OF COPPER FROM METAL
02/11/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
L 5 TRS TESTING OK; NEED TO SEE PIPE INSULATION
ISOLATION FROM METAL AND VENT CONNECTION
ALSO, HAMMER ARRESTORS & CLOSET FLANGES
02/06/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
LEVELS 3 & 4 PIPE INSULATION OK
SECURE W/CORRECT SIZE CLAMPS
INSTALL FHA STRAPS WITHIN 1 1/4
OK TO COVER WALLS IN LEVEL 3 & 4 TOILET RMS
01/29/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- LEVEL 4 DWV & DOM. WATER TEST OK
- HAMMER ARRESTORS REQUIRED ON ALL BRANCH PIPING TO FLUSH-O-METERS
- BRACE VENTS
- INSULATE HW RECALL FOR INSPECTION
- SUPPORT WATER PIPING AT LAVS
- RISER CLAMPS ON C1 THRU FLOOR
- SUPPORTS REQUIRED ON EACH END OF C1
- CALL FOR ROOF DRAIN INSPECTION - 03037
6" RWL AT 1/K TESTED TO ROOF
01/25/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
3RD FLOOR RESTROOMS OK
NEED TO SEE PIPE INSULATION
WILL INSPECT CLOSET FLANGES AFTER FF
01/22/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
RWL IN EAST CHASE W/TEST THRU ROOF OK
DWV WEST CHASE W/TEST THRU ROOF OK
01/16/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSTALL SOLID PIPE SUPPORTS ON CAST IRON IN CHASE PIPING WET. POSSIBLE LEAKS.
RECALL FOR INSPECTION
01/15/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV IN CHASE TO 3RD LEVEL OK
DOMESTIC WATER W/90 PSI TEST OK
12/28/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- BRANCH PIPING SERVING DOMESTIC WATER TO 1ST & 2ND LEVEL
- TOILET RMS OK TO INSULATE
- ALL BRANCH LINES SERVING FLUSH-O-METER VALVES REQUIRE WATER HAMMER ARRESTORS PER UPC SEC 609.10
11/27/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
11/13/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DOMESTIC WATER PIPING LEVEL 3 EAST OF COL G TEST OK
2) REMOVE ANY EXCESS FLUX PRIOR TO INSULATION. SUPPORTS AT EAST END
3) DOMESTIC WATER SERVICE PIPING OK PROVIDE TEST
4) INSTALL CORRECT SIZE VENT FITTING AT 1ST FLOOR TRS AND RETEST
5) TEST ON WASTE PIPING 1ST AND 2ND LEVEL TO 9' ABV 2ND LEVEL OK
11/01/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WATER PIPING LEVEL 2 OK
10/24/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
ROOM #110 WATER TEST OVERHEAD OK FOR WATER PIPING
10/03/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV FROM FF TO CEILING OF LEVEL 2 W/TEST