Permit: T06CM05804

Parcel: 13317064B

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T06CM05804

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
08/14/2008 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
03/10/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
SOIL/SEWER PIPING AROUND VAULT IN NE CORNER
OK TO COVER
HARD CAP PVC
TERMINATE CLEANOUTS
07/02/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
- ROUGH SOIL AT TRS PER REDLINES AND JS AND DF
OK TO COVER
- RWL TO 14' IN COLS FOR CANOPY OK
- DRAIN PIPING IN VAULT TO 15' OK
06/29/2007 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
REDLINES NOT INSTALLED PER PLAN - SHALL BE COMPLETE PRIOR TO INSPECTION.
CORRECT SLOPE ON TRAP ARMS
06/22/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
4' ROUGH SOIL BETWEEN COLS G & H OK
REDLINE CHANGE AT TOILET RM
SHADE PIPE W/CLEANFILL - NO CHUNKS
HAVE WATER IN PIPING WHILE BACKFILLING
NEED TO SEE CONNECTION TO SEWER
06/21/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
ROUGH SOIL BETWEEN I AND J OK TO COVER
06/20/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
ROUGH SOIL BETWEEN K&L W/TEST AND HUSKY SD 4000
BANDS. OK TO COVER. CANOPY RWL IN COLUMNS OK WRAP W/FOAM
06/19/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
ROUGH SOIL W/TEST BETWEEN K & L AND 1 & 12
WITH RISERS FOR UPPER FLOORS AND CLEANOUTS
SPEC 2.01 SPECIFIES HUSKY SD4000 BELOW GRADE
06/05/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
100 PSI TEST ON ELEVATOR SUMP DRAIN. OK TO COVER.
06/01/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
2" COPPER FROM ELEVATOR PIT PER REDLINE P1.1 AS INSTALLED OK
SHALL PROVIDE TEST ON PIPING FOR OK
05/07/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
PIPING COL. K-M AND COL 1-4 INSTALLED IN VAULT AREA
CONCRETE PER PLAN OK TO POUR
USE EXTRA THICK PIPE WRAPS
04/17/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
JIM W/DIVERSIFIED
2" TYPE INSTALLED AT SUMP PIT TO WEST WALL
REDLINE CHANGE OF LOCATION