Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM05804
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/14/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/13/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. INSPECTED PENTHOUSE AND FLOORS 2-5 2. INSTALL ARCH FLASH WARNING LABLES 3. SOME EM LIGHTS NOT WORKING 4. FINISH INSTALLING LIGHTS IN CORRIDORS 5. NEED DISCONNECTING MEANS FOR COOLING TOWER MOTORS PER NEC 430.102 (B) 6. NEED SIGN FOR GENERATOR @ SERVICE ENTRANCE - NEC 700.8 |
|
08/12/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* INSPECTION OF OUTDOOR LIGHTS ONE EM @ SOUTHWEST CORNER NOT WORKING |