Permit: T06CM05804

Parcel: 13317064B

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
08/14/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
08/11/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING 2ND FLOOR CORRIDOR. ENSURE TEMP WIRING IS REMOVED. NEED CONNECTORS WHERE THERMOSTAT CABLE ENTERS AIR HANDLERS
07/31/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILINGS 4TH FLOOR CORRIDOR. ENSURE TEMP WIRING IS REMOVED
07/29/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILINGS 3RD FLOOR CORRIDOR
ENSURE TEMP LIGHTS GET REMOVED
07/28/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK RECESSED FIXTURES IN SOFFITS ABOVE DOORS DOWN MAIN CORRIDOR 4TH FLOOR
07/23/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING 5TH FLOOR CORRIDOR
07/10/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING ELEVATOR LOBBY & OUTSIDE RESTROOMS
2ND FLOOR
06/20/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILINGS ELEVATOR LOBBY & OUTSIDE RESTROOMS
FLOORS 3, 4, 5
06/17/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. BOXES NOT FLUSH WITH BOTTOM OF TILES WILL NEED EXTENDER RINGS -- 314.20
2. DISCONNECTS TO BE MOUNTED NOT FACING DOWN

OK EXCEPT 2ND FLOOR DISCONNECTS
03/20/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. PROTECT VDV CABLES FROM SHARP METAL EDGES
2. PLEASE VERIFY IF 4-11 BOX IS RATED FOR GROUNDING OVER 250V

OK LOBBY SOFFIT 1ST FLOOR
OK ENTRANCE CANOPY AFTER CORRECTIONS
02/26/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK DRIVE CANOPY CANS