Permit: T06CM05804

Parcel: 13317064B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/14/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/06/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS PENTHOUSE
02/01/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 5TH FLOOR HALL & BATHROOM & ELECTRIC ROOM
01/25/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
BUILDING INSPECTOR TO CHECK FIRE STOPPING

OK FLOOR 3 & 4 BATHROOMS & ELECTRIC ROOMS
01/16/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TEMP POWER HP-1
12/28/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK AS MARKED WITH GREEN STICKERS
CONTRACTOR TO MAINTAIN LO/TO

1. NEED DOORS BEFORE FINAL
12/21/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROTECT CONDUCTORS AT CONDUITS 300.4, 352.46
2) BRACE CABLES AS PER MANUFACTURERS REQUIREMENTS
3) DOOR MODIFIED IN FIELD TO BE CERTIFIIED BY 3RD PARTY LISTING AGENCY
4) OK 1ST & 2ND FLOOR BATHROOMS
5) OK MAIL ROOM
6) RECEIVED GFI TEST AND TORQUE LETTER
12/03/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
11/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK POLE HEADS VAIL LOT
2) OK CONDUIT AGAINST SHAFT 4 AND 5TH LEVEL
11/02/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS IN CORRIDOR 4TH FLOOR
10/30/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
POST BOND FOR POWER FINISH PREVIOUS ITEMS
10/26/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 4 POLE BASES LOT
OK HALL CORRIDOR 3RD FLOOR

SPLICES TO BE FOR WET LOCATION
10/04/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
10/02/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. DO NOT COVER AREAS WITHOUT INSPECTIONS

OK 2ND FLOOR CORRIDOR
09/11/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK CONDUITS IN BLOCK LOBBY
OK CONDUITS & SUPPORTS SIDE OF ELEVATOR SHAFT
OK POLE TO POLE 3/4" PVC
OK POLE TO SERVICE 3/4" PVC
BENSON LOT
07/23/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 3RD LIFT
07/17/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 2ND LIFT
07/09/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 13 - 4" PVC BUILDING TO FENCE
OK 1ST LIFT BOXES & CONDUIT STAIRWELL/STORAGE
06/27/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK PVC CONDUIT FOR SES & DISTRIBUTION CENTERS
OK 2ND & 3RD LIFTS AT CANOPY COLUMN

SAND FILL TO AVOID CONDUIT BREAKAGE
06/20/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK COLUMN CONDUIT ENTRY
1. NOTE 300.7