Permit: T06CM05804

Parcel: 13317064B

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
04/16/2008 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
ELEVATOR DOOR INFILLS AS PER RFI DATED 7 AUG 08
FLOORS 1-5 OK TO GROUT
01/25/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
DUMPSTER AREA WALLS ALL TOPPED OUT @ 6'4"
GROUTED -- OK TO CAP
01/22/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1ST LIFT @ 0-4'
EAST DUMPSTER OK TO POUR
12/19/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST STAIRWELL #1, ELEVATOR, ROOM #601: ALL @ 80'8"
TOPPED OUT
12/17/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
LOBBY ELEVATOR 80'8"; 502-506 W,S,E WALLS @ 80'8"
OK TO GROUT
12/13/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
ELEVATOR LINE G/2 TO G/9 @ 72'8"; ROOMS #502-506
WEST, NORTH, SOUTH WALLS @ 72'8" -- OK TO GROUT
12/10/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
LOBBY; #502-506; LINE G/1-5 TO 10.5;
STAIRWELL #1 - ALL @ 72' -- OK TO GROUT
12/07/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
STAIRWELL #1
W-N-SOUTH WALLS @ 68'-72'
ELEVATOR WALL @ 68'-72' -- OK TO GROUT
12/05/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
ROOMS #502-506, 64' TO 68'; NORTH, SOUTH, WEST
WALLS: WEST ELEVATOR - STAIRWELL #1 - N.W.S WALLS
64' TO 68' OK TO GROUT PROGRESS AREAS (*)

(*) - S.W MECHANICAL ROOM WALLS @ 0'-9'4" -- OK TO GROUT
12/03/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
#502-506 @ 64'; 3RD FLOOR LOBBY #301 - 3' RADIUS WALL
OK TO GROUT
11/29/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
ROOMS 502-506 @ 59'; #1 STAIRWELL WALLS @ 67';
WEST ELEVATOR @ 64' -- OK TO GROUT PROGRESS AREAS
11/26/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
STAIRS #1 & ELEVATOR @ 59' -- OK TO GROUT
11/20/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
LOBBY CMU WALL @ 64' - LINE G TO 9
11/19/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
STAIRWELL #1, EAST WALL; LOBBY EAST WALL;
ROOM #506 EAST WALL
CHASE WALL EAST - ALL @ 59' - GRID LINE G/1.5 TO G/10.5
GROUTED
11/13/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) STAIRWELL #1, ELEVATOR (WEST), #402-406 AT 55'
11/08/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
STAIRWELL #1, WEST ELEVATOR; ROOMS 402-406
ALL @ 50' -- OK TO GROUT
11/05/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
WEST ELEVATOR LOBBY WALL @ 50';
ROOM 402-406 @ 46' OK TO GROUT
11/01/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
ELEVATOR (WEST) LOBBY WALL @ 44'
ROOM 302-306 @ 40'
OK TO GROUT
10/30/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
WEST STAIRS @ 40'; ELEVATOR @ 40', ROOM #402-406 @ 36'
OK TO GROUT
10/26/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
STAIRWELL #1 @ 36'
VAIL PARKING LOT 4 @ LIGHT POLE COLUMN FOOTINGS
OK TO POUR
10/24/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
STAIRWELL #1 @ 32'; G LINE 1.5 TO 10.5 @ 36'
ROOM #302-306 @ 321
OK TO GROUT PROGRESS AREA
10/22/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
STAIRWELL #2 @ 32'
INTERIOR WALL LINE G/1.5-10.5 @ ELEVATOR 32'
OK TO GROUT
10/19/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
WEST STAIRWELL #1 @ 20';
INTERIOR MECHANICAL CHASE @ 31'
EAST STAIRWELL CAPPED @ 68'
OK TO GROUT - PROGRESS AREAS
10/18/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
2ND FLOOR MECHANICAL CHASE @ 19' -- OK TO GROUT
10/17/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST STAIRWELL INTERIOR WALLS @ 64'
#1 STAIRWELL (WEST) @ 28' -- OK TO GROUT PROGRESS AREAS
10/16/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST STAIRWELL INTERIOR WALLS @ 64'; OK TO GROUT
10/15/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST STAIRWELL @ 74'4" (WEST WALL);
LOBBY ENTRANCE @ 18'
STAIRWELL #1 @ 20' -- OK TO GROUT
10/11/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST ELEVATOR @ 74'8" TOPPED OUT
OK TO CAP & GROUT
10/10/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
WEST ELEVATOR FASCIA WALL - 28' OK TO GROUT
10/09/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST ELEVATOR @ 68' TO 72'
LOBBY INTERIOR WALLS @ 28'8" -- OK TO GROUT
10/08/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST STAIRWELL @ 68'; OK TO GROUT
10/04/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) LOBBY INTERIOR WALLS AT 28'; WEST ELEVATOR FACING AT 24' OK TO GROUT
10/03/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
LOBBY INTERIOR WALLS @ 20' - OK TO GROUT
10/02/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST STAIRWELL @ 64'
WEST ELEVATOR - CMU WALLS @ 28' -
LOBBY INTERIOR WALLS @ 18' - OK TO GROUT
10/01/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
- EAST ELEVATOR @ 62',
- WEST ELEVATOR (INTERIOR) FACING @ 20'
- LOBBY INTERIOR WALLS @ 16' - OK TO GROUT PROGRESS AREAS

* TRASH ENCLOSURE @ 6' - OK TO GROUT & CAP
BENSON PARKING LOT - CONCRETE DRAINAGE GUTTER
SE CORNER - MESH INSTALLED AS PER PLANS OK TO POUR
09/26/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST STAIRWELL @ 56'; LOBBY INTERIOR WALLS @ 12'
OK TO GROUT
09/25/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
LOBBY ELEVATOR @ 18'
OK TO GROUT
09/24/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST STAIRWELL @ 52'
LOBBY INTERIOR WALLS @ 12' OK TO GROUT
09/21/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST STAIRWELL @ 48'; LOBBY EXTERIOR RADIUS WALL NW,
LINE B.5/3.5 TO F.5/2.5; INTERIOR LOBBY WALLS @ 8'
OK TO GROUT PROGRESS AREAS
09/19/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) EAST STAIRS AT 44'; LOBBY EXTERIOR WALLS AT 18'; LOBBY INTERIOR WALLS AT 4'-OK TO GROUT PROGRESS AREA
09/17/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST STAIRWELL #2 @ 40'
WEST MAIN ENTRY WALL - LINE A/3 TO C/11.5 @ 16'
OK TO GROUT PROGRESS AREAS
09/13/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST STAIRWELL @ 36'; ELEVATOR FACE WALL @ 16' OK TO GROUT PROGRESS AREAS
09/12/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST STAIRWELL @ 32';
ELEVATOR FACE WALL @ MAIN ENTRY @ 12' -- OK TO GROUT
09/10/2007 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
WILL RECALL
09/07/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST STAIRWELL @ 28'; LOBBY WALLS @ 12'
OK TO GROUT
09/05/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST STAIRWELL #2 @ 24'; LOBBY EXTERIOR WALLS @ 8'
OK TO GROUT PROGRESS AREAS
09/04/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
E. STAIRWELL (#2) @ 20' (EXTERIOR BRICK)
LOBBY EXTERIOR WALLS & ENTRY AREA @ 4'
ELEVATOR SHAFT (WEST) @ 20' : OK TO POUR
08/28/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
LINES G/1 - 1.5 @ 18'
1/G TO M @ 18'
M/1-7 @ 18'
WEST STAIRWELL (W & N) WALLS @ 16'
OK TO GROUT
08/24/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
NORTH WALL @ 16' LINES
G/1 TO 1.5 @ 16'
COLUMN LINE 1-G TO M @ 16'
COLUMN LINE M/1 - 7 @ 16' OK TO GROUT
08/22/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
SOUTH WALL LINE 12 G TO M
G/11-12
M/11-12 @ 18' OK TO GROUT
LINE 1 G TO M
G/1 TO 1.5
M/1-7 @ 12' OK TO GROUT
08/20/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) COLUMN LINE #1-G TO M; COLUMN LINE G/1 TO 1.5 ?/1 TO 7 AT 8'-OK TO GROUT
08/16/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
SOUTH WALL: LINE G-M; G/11-12
M/11-12 @ 16' -- OK TO GROUT
08/14/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
COLUMN LINE 1/G TO "M"
G/1 TO 1.5
M/1 TO 7 @ 4' OK TO GROUT
08/13/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
SOUTH WALL G-M @ 12'
M/11 - M/12
G/11 - G/12 @ 12'
OK TO GROUT PROGRESS AREA
08/10/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) EAST STAIRWELL AT 28' LINE M/7 TO M/11
2) OK TO GROUT
08/08/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
SOUTH WALL
LINE M/11-M/12
G/11 - G/12 @ 8'
OK TO POUR
08/07/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
SOUTH WALL 11-12 (M)
11-12 (G) @ 4'
OK TO GROUT
08/06/2007 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELLED
RAINED OUT
08/02/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST STAIRWELL M-M.5; COLUMN LINE 7-11 @ 24'
OK TO POUR
07/31/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
WEST STAIRWELL: G/1.5 TO G/11 @ 16'
EAST STAIRWELL M/M.5; COLUMN LINE 7-11 @ 20'
07/26/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST STAIRWELL, CORRIDOR, STORAGE: LINES 7-11,
M-M.5 @ 16' -- OK TO GROUT
07/24/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
COLUMN LINE 1.5 TO 11; F-G; WEST STAIRWELL ELEVATOR
BACK WALL TO RESTROOMS @ 8'
07/23/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST STAIR, CORRIDOR, STORAGE: LINES 7-11; M/5 @ 12'
OK TO POUR
07/19/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
WEST STAIRWELL, LINE G/1.5 TO G/4 @ 8';
ELEVATOR WEST LINE G/4 TO G/9 @ 4' --- OK TO GROUT
07/17/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
STAIRWELL #2, EXIT VESTIBULE; STORAGE @ 8' -
OK TO GROUT
07/13/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
WEST STAIRWELL @ 0'-4' OK TO GROUT
07/11/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
LOBBY - RESTROOMS (#101); ELECTRIC ROOM, JANITOR ROOM,
MAIL ROOM @ 12"; VAULT N & E WALL @ FINISH FLOOR
OK TO GROUT PROGRESS AREAS
07/10/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST STAIRWELL #2 & STORAGE & VESTIBULE @ 4'
OK TO GROUT
06/29/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
CANOPY COLUMNS @ 14' -- NW & SW OK TO GROUT
06/27/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
CANOPY COLUMNS NW/SW - NE/SE @ 12' OK TO GROUT
06/20/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
4 @ CANOPY COLUMNS @ 4' ABOVE FINISH FLOOR
OK TO GROUT
06/11/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EXTERIOR CONTINUOUS SHELL STEM WALLS;
4 @ CANOPY COLUMNS, FIRST LIFT: OK TO POUR/GROUT
05/31/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
LINE D/3 TO F.5/3; D/10 TO G/10 -- OK TO GROUT
05/29/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
WALL LINE #1 -- J TO K.5 (95' TO 99'4")
STEM WALLS @ 91' TO 95' A TO G
G/10.8 TO G/11.2
OK TO GROUT