Permit: T06CM05782

Parcel: 137055110

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM05782

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/20/2009 ELECTRIC - FINAL Approved ONLY OUTSTANDING ELECTRIC ISSUE WAS REVIEW OF AS-BUILTS. REVISIONS OK. INSPECTION APPROVED.
02/05/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NO REVISION SUBMITTED TO DSD PER INSP. 10/1/08
2. TCO EXPIRED
10/01/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
OK #12 EXPOSED CONDUCTORS

1. SIGN READER BOARD HAS CORD THROUGH WALLS AND ABOVE CEILINGS
2. PLAN REVISIONS TO BE FOR NEON ON BUILDING AND NEW LIGHTS ON BLADE

ALSO, NEED LIGHTING CALCULATION PER OUTDOOR LIGHTING
07/11/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
OK TO COVER RISER SIDE

OTHER SIDE COVERED IN MUD CANNOT SEE WHAT WAS DONE

INSPECTOR WILL NOT MAKE NEW LIST - FOLLOW PREVIOUS INSPECTIONS
07/01/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
06/18/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
NEON ITEM ALL CORRECTED

1. FINISH ITEMS #12 & 4 PREVIOUS INSPECTION AND
PLAN REVISIONS

*OUTSIDE LIGHTS NEED INSPECTION (ON BLADE)
06/09/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK INSIDE CORRECTIONS EXCEPT TO VERIFY SIGNAGE AND NEON LTG.
06/05/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
NEED SIGN CONTRACTOR ON SITE TO ACCESS TO INSPECT
ALSO CALL SIGN PERMIT
05/06/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
INTERIOR:
1. SIGN SWITCHES TO BE EXTERNALLY OPERABLE - 600.6
2. MARKING LABELS NEEDED AND FILLED OUT
3. FILL UNUSED OPENINGS
4. BOND FLEX RACEWAYS WITH GTO
5. SPACE LED DRIVERS OF WOOD FOR HEAT & CIRCULATION
6. PROVIDE TRANSITION PLATES AT DRYWALL FOR GTO RACEWAYS
7. PROPERLY USE BOOTS INSIDE OF RACEWAYS
8. BOND METAL OF SIGNS ALSO LED LETTERS
9. USE APPROVED HARD WIRE TO HANG SIGNS NOT DRYWALL SCREWS
10. SWITCH TO BE CAPABLE OF BEING LOCKED OUT
11. HANDY BOX OVERFILLED
12. NO EXPOSED CONDUCTORS INSIDE OF CABINETS

EXTERIOR:
1. GTO TO HAVE WEATHERPROOF SLEEVING
2. TIGHTEN LOOSE FITTING
3. GTO LENGTH TO FIRST TUBE NOT TO BE
OVER 20' (600.32 (J) (I)
4. PROPERLY WIRE READER BOARDS
5. USE CORRECT COLOR CONDUCTORS IN RACEWAY FOR 277V

*CK ROOF NEXT TIME
*WILL NEED NEON PLANS REVISED FOR BLADES & INSIDE WALL SIGNS
05/05/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
SEE NOTES LAST INSPECTION FOR GFI REQUIREMENTS
IN CONCESSION AREA PER 210.8 NEC (2002)
04/29/2008 ELECTRIC - FINAL Partial Approval - CK ROOF EQUIP.
- OK COUNTING ROOM & OFFICE
- SUPPORT FLEX IN TELECOM ROOM CEILING
- CK PANEL SCHEDULES
- CK RECEPTS IN CORRIDORS FOR SPACING