Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T06CM05782
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/01/2008 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* ELECTRICAL CONTR. TO BE RESPONSIBLE TO ONLY ALLOW AUTHORIZED PERSONNEL TO HAVE ACCESS TO ELECTRICAL EQUIP. FOR SAFETY |
|
12/26/2007 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | IVRS - Inspection :*. 1) TIGHTEN ALL CONDUCTORS TO LUGS 2) DO NOT STACK LUGS 3) BRACE CONDUCTORS PER MANUFACTURERS REQUIREMENTS 4) FILL UNUSED OPENINGS IN DISCONNECTS 5) INSTALL NEUTRALS TO MAIN DISCONNECTS PER PLANS AND CODE 6) INSTALL MAIN BONDING JUMPERS 7) CANNOT TRIM CONDUCTORS 8) RISERS NOT PER PLANS 9) PLEASE VERIFY INSPECTIONS OF CONDUCTORS TO BLDG 10) ONLY ONE CONDUCTOR PER LUG 11) CANNOT USE SHEET METAL THREAD SCREWS FOR GROUNDING 250.8 12) NEED PHYSICAL PROTECTION FOR #8 ? AND UN-COVER GROUND RODS 13) FINISH INTERIOR |
|
09/25/2007 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* - NEUTRAL CONDUCTOR REQUIRED IN ADDITION TO PHASE CONDUCTORS FROM TEMP SERVICE EQUIP. TO POLE RISER PLEASE CONSULT WITH TEP FOR NEUTRAL REQUIREMENTS AS WELL AS 250-24 NEC - NEUTRAL TO BE RUN TO SERVICE DISCONNECTS PER 250 NEC |
|
09/20/2007 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | IVRS - Inspection :* |