Permit: T06CM05782

Parcel: 137055110

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Permit Number - T06CM05782

Inspection Description - ELECTRIC - TEMPORARY SERVICE

Inspection Status - Approved

Date Description Inspector Results Comments
04/01/2008 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection :*
ELECTRICAL CONTR. TO BE RESPONSIBLE TO ONLY ALLOW AUTHORIZED PERSONNEL TO HAVE ACCESS TO ELECTRICAL EQUIP. FOR SAFETY
12/26/2007 ELECTRIC - TEMPORARY SERVICE Not ready for Inspection IVRS - Inspection :*.
1) TIGHTEN ALL CONDUCTORS TO LUGS
2) DO NOT STACK LUGS
3) BRACE CONDUCTORS PER MANUFACTURERS REQUIREMENTS
4) FILL UNUSED OPENINGS IN DISCONNECTS
5) INSTALL NEUTRALS TO MAIN DISCONNECTS PER PLANS AND CODE
6) INSTALL MAIN BONDING JUMPERS
7) CANNOT TRIM CONDUCTORS
8) RISERS NOT PER PLANS
9) PLEASE VERIFY INSPECTIONS OF CONDUCTORS TO BLDG
10) ONLY ONE CONDUCTOR PER LUG
11) CANNOT USE SHEET METAL THREAD SCREWS FOR GROUNDING 250.8
12) NEED PHYSICAL PROTECTION FOR #8 ? AND UN-COVER GROUND RODS
13) FINISH INTERIOR
09/25/2007 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999*
- NEUTRAL CONDUCTOR REQUIRED IN ADDITION TO PHASE CONDUCTORS FROM TEMP SERVICE EQUIP. TO POLE RISER
PLEASE CONSULT WITH TEP FOR NEUTRAL REQUIREMENTS AS WELL AS 250-24 NEC
- NEUTRAL TO BE RUN TO SERVICE DISCONNECTS PER 250 NEC
09/20/2007 ELECTRIC - TEMPORARY SERVICE Not ready for Inspection IVRS - Inspection :*