Permit: T06CM05782

Parcel: 137055110

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM05782

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/01/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
04/18/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK ELECTRICAL, TICKET COUNTER, HOWEVER ALL LOW VOLTAGE CABLING MUST COMPLY WITH 725 THRU 800 NEC
INSTALL IN WORKMANSHIP LIKE MANNER, SUPPORT TO STRUCTURE NOT WIRES FOR GRID CEIING OR ELECTRICAL
CANNOT APPROVE ABOVE CEILING THIS AREA UNTIL DONE
04/16/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
- CONTACT JESSIE @ 955-0520 MTN. POWER
- CK EXT. RING IN LOBBY & HALLWAYS
- OK ABOVE CEILING OVER CONCESSION AREA
04/07/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
- OK PARTIAL ABOVE CEILING CENTER 2ND FLOOR
WILL NEED TO RECHECK AFTER TEMP LTG. REMOVED
03/31/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
- GROUNDS IN BOND BUSHINGS AT SERVICE FEEDS TO DIST. PANELS TO SMALL ALSO, AT DIST. PANELS
- RECEIVED LETTERS FOR TORQUE, FEEDERS, USE OF MC
- OK ABOVE CEILINGS 2ND FLOOR NORTH & SOUTH WINGS OFFICE SECTION NOT READY
03/28/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONTACT PERSON JESSIE @ 955-0520

- SEISMIC WIRES TO BE TIED AT BOTH ENDS
- MC CABLE TO BE SUPPORTED WITHIN 12" OF TERMINATIONS
AND AT 6' INTERVALS
- THERE ARE OPEN J-BOXES
- DO NOT SUPPORT MC TO OTHER CONDUITS
03/14/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
DO NOT ONE SIDE WITHOUT CLEARANCES
03/11/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
- OK ABOVE CEILING #18 AUDITORIUM
- OK DORMITORY WALLS
03/05/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/04/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/29/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
- PROVIDE LETTER OF APPROVAL FOR USE OF MC CABLE IN HARD LIDS - SEE SPEC'S
- OK ABOVE GRID #12, #13, #14, #15, #17 AND AUDITORIUMS
02/28/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
MC TO BE STRAPPED PER CODE WITHIN 12" OF BOX
OR TERMINATION AND AT 6' INTERVALS PER NEC
02/26/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/25/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/20/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/13/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
- OK ABOVE CEILING AUDITORIUM #7, #8, #9, #10
- CALL JESSIE 955-0520 MTN. POWER
02/12/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
CANCELED
02/11/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
- OK #2 AUDITORIUM CEILING ONLY
- OK PARTIAL 3/0 GROUNDING U.G NEED TO SEE CONNECTION TO WATER, GAS BLD. STEEL
02/06/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/04/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/01/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
01/31/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
01/30/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
01/22/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
PARTIAL AUDITORIUM #1 THRU #9 CALL FOR REINSPECTION
AFTER GRID INSTALLED.