Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM05782
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/01/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
04/18/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK ELECTRICAL, TICKET COUNTER, HOWEVER ALL LOW VOLTAGE CABLING MUST COMPLY WITH 725 THRU 800 NEC INSTALL IN WORKMANSHIP LIKE MANNER, SUPPORT TO STRUCTURE NOT WIRES FOR GRID CEIING OR ELECTRICAL CANNOT APPROVE ABOVE CEILING THIS AREA UNTIL DONE |
|
04/16/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - CONTACT JESSIE @ 955-0520 MTN. POWER - CK EXT. RING IN LOBBY & HALLWAYS - OK ABOVE CEILING OVER CONCESSION AREA |
|
04/07/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - OK PARTIAL ABOVE CEILING CENTER 2ND FLOOR WILL NEED TO RECHECK AFTER TEMP LTG. REMOVED |
|
03/31/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - GROUNDS IN BOND BUSHINGS AT SERVICE FEEDS TO DIST. PANELS TO SMALL ALSO, AT DIST. PANELS - RECEIVED LETTERS FOR TORQUE, FEEDERS, USE OF MC - OK ABOVE CEILINGS 2ND FLOOR NORTH & SOUTH WINGS OFFICE SECTION NOT READY |
|
03/28/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* CONTACT PERSON JESSIE @ 955-0520 - SEISMIC WIRES TO BE TIED AT BOTH ENDS - MC CABLE TO BE SUPPORTED WITHIN 12" OF TERMINATIONS AND AT 6' INTERVALS - THERE ARE OPEN J-BOXES - DO NOT SUPPORT MC TO OTHER CONDUITS |
|
03/14/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* DO NOT ONE SIDE WITHOUT CLEARANCES |
|
03/11/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - OK ABOVE CEILING #18 AUDITORIUM - OK DORMITORY WALLS |
|
03/05/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
03/04/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
02/29/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - PROVIDE LETTER OF APPROVAL FOR USE OF MC CABLE IN HARD LIDS - SEE SPEC'S - OK ABOVE GRID #12, #13, #14, #15, #17 AND AUDITORIUMS |
|
02/28/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* MC TO BE STRAPPED PER CODE WITHIN 12" OF BOX OR TERMINATION AND AT 6' INTERVALS PER NEC |
|
02/26/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
02/25/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
02/20/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
02/13/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - OK ABOVE CEILING AUDITORIUM #7, #8, #9, #10 - CALL JESSIE 955-0520 MTN. POWER |
|
02/12/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
02/11/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - OK #2 AUDITORIUM CEILING ONLY - OK PARTIAL 3/0 GROUNDING U.G NEED TO SEE CONNECTION TO WATER, GAS BLD. STEEL |
|
02/06/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
02/04/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
02/01/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
01/31/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
01/30/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
01/22/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* PARTIAL AUDITORIUM #1 THRU #9 CALL FOR REINSPECTION AFTER GRID INSTALLED. |