Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM05782
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/01/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* 1. INSTALL SIGNAGE FOR PANELS FED BY EM. GEN. 2. OK ROOF EQUIP. OK EM. GENERATOR TEST RECEIVED GEN. TEST INFO. 3. KITCHEN RECEPTS (120V) TO BE GFI PROTECTED PER 210.8 NEC 4. COMPLETE INTERIOR SIGNAGE OK TCO FOR STOCKING & TRAINING |
|
04/05/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | CHECK GAP BETWEEN DEVICES & SOUND BOARD, INSTALL BOX EXTENDERS WHERE NECESSARY |
|
03/18/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK WATER, GAS, BLD. STEEL, BONDING, MAIN BOND JUMPER IN SES OK - PROVIDE LETTER OF TORQUE FOR SES - LETTER FROM ARCH FOR CHANGE OF FEEDER SIZES & MATERIAL - OK GAME & CHILDRENS AREA WALLS - POST BOND FOR TEMP POWER FOR TEST |
|
03/06/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK RESTROOMS BY AUDITORIUM #11 - OK CEILING IN #16 AUDITORIUM - OK WALLS PROMANADE SECTION #2 |
|
03/05/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WOMENS RESTROOM BY AUDITORIUM #18 SUBJECT TO LETTER OF MC APPROVAL |
|
03/04/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK GUEST SERVICE & BOX OFFICE WALLS, SUBJECT TO MC APPROVAL - OK RESTROOMS BY AUDITORIUM #8 |
|
02/26/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK ABOVE CEILING AUDI. #1 - OK HARD LID AT SOUTH ENTRANCE - OK SECOND FLOOR OFFICE WALL ROUGH |
|
02/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK ENTRANCE AREA #3 ROUGH - BEND OUT TABS FOR 2X4 LAY IN FIXTURES OR USE #8 SCREWS TO GRID |
|
02/20/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK LOBBY WALLS - OK ENTRANCE TO AUDITORIUMS #2, 4, 5, 6, 7 - OK NORTH ENTRANCE HARD LIDS |
|
02/06/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK CEILING #5 AUDITORIUM - OR ROUGH WALLS EXCEPT SMALL PARTITIONS AT ENTRANCE #15, #16 |
|
02/04/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK PARTIAL FOR 3, 4, 6 AUDITORIUMS. LIGHTING OK, COMPLETE FA, VIDIO, ANY LV WIRING BEFORE TILE |
|
02/01/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK EXTERIOR WALLS AUDITORIUM #13, #14 - OK LOBBY UPSTAIRS WALL |
|
01/31/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 955-0520 CONTACT PERSON (JESSE W/MTN. POWER) OK WALLS & PARTIAL CEILINGS, NO GRID YET #'S 11, 12, 17 AUDITORIUMS |
|
01/30/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
01/09/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROUGH FOR AUDITORIUM WALLS #1 THRU #9 AND CORRIDOR SECTION #1 WALLS |
|
10/01/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WIRING METHOD FOR TILT UP CONCRETE PANELS TYP. OF ALL PANELS |