Permit: T06CM05782

Parcel: 137055110

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM05782

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/01/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
1. INSTALL SIGNAGE FOR PANELS FED BY EM. GEN.
2. OK ROOF EQUIP. OK EM. GENERATOR TEST RECEIVED GEN. TEST INFO.
3. KITCHEN RECEPTS (120V) TO BE GFI PROTECTED
PER 210.8 NEC
4. COMPLETE INTERIOR SIGNAGE

OK TCO FOR STOCKING & TRAINING
04/05/2008 ELECTRIC - INTERMEDIATE Partial Approval CHECK GAP BETWEEN DEVICES & SOUND BOARD,
INSTALL BOX EXTENDERS WHERE NECESSARY
03/18/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK WATER, GAS, BLD. STEEL, BONDING, MAIN BOND JUMPER IN SES OK
- PROVIDE LETTER OF TORQUE FOR SES
- LETTER FROM ARCH FOR CHANGE OF FEEDER SIZES & MATERIAL
- OK GAME & CHILDRENS AREA WALLS
- POST BOND FOR TEMP POWER FOR TEST
03/06/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK RESTROOMS BY AUDITORIUM #11
- OK CEILING IN #16 AUDITORIUM
- OK WALLS PROMANADE SECTION #2
03/05/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WOMENS RESTROOM BY AUDITORIUM #18
SUBJECT TO LETTER OF MC APPROVAL
03/04/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK GUEST SERVICE & BOX OFFICE WALLS, SUBJECT TO MC APPROVAL
- OK RESTROOMS BY AUDITORIUM #8
02/26/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK ABOVE CEILING AUDI. #1
- OK HARD LID AT SOUTH ENTRANCE
- OK SECOND FLOOR OFFICE WALL ROUGH
02/25/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK ENTRANCE AREA #3 ROUGH
- BEND OUT TABS FOR 2X4 LAY IN FIXTURES OR
USE #8 SCREWS TO GRID
02/20/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK LOBBY WALLS
- OK ENTRANCE TO AUDITORIUMS #2, 4, 5, 6, 7
- OK NORTH ENTRANCE HARD LIDS
02/06/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK CEILING #5 AUDITORIUM
- OR ROUGH WALLS EXCEPT SMALL PARTITIONS AT
ENTRANCE #15, #16
02/04/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK PARTIAL FOR 3, 4, 6 AUDITORIUMS. LIGHTING OK, COMPLETE FA, VIDIO, ANY LV WIRING BEFORE TILE
02/01/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK EXTERIOR WALLS AUDITORIUM #13, #14
- OK LOBBY UPSTAIRS WALL
01/31/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
955-0520 CONTACT PERSON (JESSE W/MTN. POWER)

OK WALLS & PARTIAL CEILINGS, NO GRID YET
#'S 11, 12, 17 AUDITORIUMS
01/30/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/09/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROUGH FOR AUDITORIUM WALLS #1 THRU #9 AND CORRIDOR SECTION #1 WALLS
10/01/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WIRING METHOD FOR TILT UP CONCRETE PANELS
TYP. OF ALL PANELS