Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/15/2009 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 03/23/2009 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO UFER INSPECTION, BLD. STEEL, WATER, GAS 2. INSTALL BUSHED ENDS ON CONDUIT ENTRIES INTO SES PER 300 AND 352.46 3. CHECK MANUF. OF SES FOR BRACING INFO SECONDARY CONDUCTORS 4. POST BOND FOR TEMP POWER FOR TEST 5. PROVIDE LETTER OF TORQUE |