03/15/2007 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
PLANS DRAWN & APPROVED IN ERROR.
IECC SECTION 803.2.8 REQUIRES MIN. R5 DUCT INSULATION NOT R3.5
PROVIDE 1 1/2" MIN. R5 DUCT LINER OR WRAP THE OUTSIDE OF THE DUCT.
INSTALL CEILING DIFFUSERS
CONDENSATE DRAIN OK
STRAP FLEX DUCTS EVERY 5'