Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T06CM05629
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/15/2007 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* PLANS DRAWN & APPROVED IN ERROR. IECC SECTION 803.2.8 REQUIRES MIN. R5 DUCT INSULATION NOT R3.5 PROVIDE 1 1/2" MIN. R5 DUCT LINER OR WRAP THE OUTSIDE OF THE DUCT. INSTALL CEILING DIFFUSERS CONDENSATE DRAIN OK STRAP FLEX DUCTS EVERY 5' |