Permit: T06CM05529

Parcel: 113094040

Inspection Status: Not Applicable

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
02/05/2015 EXT METAL CLIPS/EXT SHEATHING Not Applicable IVRS - Inspection :*
07/09/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUBMIT AS BUILT FOR MASONITE SIDING. PLAN CALLS FOR ONE COAT STUCCO SYSTEM
2) PROVIDE 1" CLEARANCE FROM COMBUSTIBLES AROUND WATER HEATER B-VENT 18" ABOVE ROOF LINE AND SECURE PROPERLY
3) EXPOSE FOOTERS TO VERIFY DEPTH PER DETAIL 5/9
4) EXPOSE H2.5 CLIPS PER DETAIL 5/9
5) EXPOSE BOTTOM PLATES TO VERIFY TREATED PLATES
6) CLOSET LIGHT FIXTURE WITHIN 12" STACKABLE COMBUSTIBLES
7) MISSING SMOKE DETECTOR MASTER BEDROOM
8) PAINT ROOF VENT ABS
9) BATH GFCI DOES NOT TEST
10) CLOSET GFCI DOES NOT TEST
11) PLAN CALLS FOR 2 X 10 24" ON CENTER 2 X 6 INSTALLED
12) STOPPED INSPECTION
13) LEFT CARD