Permit: T06CM05512

Parcel: 138041810


Addresses:

6500 S 12TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/16/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/09/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
COMPLETE #7 & #8 DISPENSER -- CALL FOR INSP.
FOR SEALOFFS, PROVIDE LETTER FROM DESIGNER OF RECORD THAT ESCO BOX COMPLIES WITH ART. 514.11 NEC FOR DISCONNECTION OF ALL CIRCUITS INCLUDING SIGNAL.
10/31/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. FILL UNUSED OPENING IN BOX
2. USE A TERMINAL END TO TERMINATE GROUNDING CONDUCTOR WITH STRANDED WIRE.
3. SEAL APPEARS TO BE PLACED INCORRECTLY. ALSO, PACK WEST SIDE SEAL OFF
(EPO)
4. PLEASE VERIFY 514.11 -- DISCONNECTION OF ALL CIRCUITS
5. DO NOT UTILIZE PUMP 5 & 6 UNTIL PASSED

OK UNDERGROUND 7 & 8
OK SEALS AT 5 & 6