Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/28/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) OK FOR FINAL |
|
| 12/22/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. MARK UNIT DATA PLATE W/PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY. 2. STRAP ALL FLEX DUCT TO DECK. 3. SUPPORT CONDENSATE DRAINS EVERY 4' & SLOPE MIN. 1/8" PER FT. PROVIDE TRAPS. 4. IDENTIFY EQUIPMENT PERMANENTLY |