Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/02/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. TIGHTEN ALL LOOSE DEVICES - NEC 406.4 2. LIGHT FIXTURES IN CLOSETS NEED 12" CLEARANCE TO SHELF -- NEC 410.8 3. PROVIDE ARC FAULT PROTECTION FOR SMOKE DETECTORS NEC 210.12 4. RECEPTACLE FACES TO BE FLUSH WITH COVER PLATE, NO TWISTED OR SETBACK - NEC 406.4D 5. NEED SWITCHED LIGHT OR RECEPTACLE IN LIVING ROOM NEC 210.70 6. AT WATER HEATER: A. PROVIDE PROPER DISCONNECTING MEANS - NEC 422.31 (NOT TOGGLE SWITCH) B. SCREW J-BOX COVER PLATE TO BOX C. STRAP MC WITHIN 12" OF TERMINATIONS - NEC 330.30 D. IDENTIFY WHITE USED AS HOT - NEC 200.6 7. USE CONNECTOR FOR ROMEX ENTERING HOOD - NEC 334 8. INSTALL DISPOSAL WIRING & COVER FOR ITS RECEPTACLE 9. EAST PORCH LIGHT NOT WORKING 10. AT SERVICE A. PANEL DIRECTORY NEEDS TO BE CORRECTLY IDENTIFIED IN A CLEAR, PERMANENT, AND LEGIBLE MANNER - NEC 408.4 B. EXPOSE GROUND RODS - NEC 250.53G C. BOND GAS PIPE - NEC 250.104 D. BURY GROUNDING ELECTRODE CONDUCTOR MINIMUM 12" OR SECURE TO STRUCTURE - NEC 300.5, 250.64 E. MAXIMUM 15 AMPS ON 14GA CONDUCTOR - NEC 310.15 11. PROVIDE SERVICE RECEPTACLE FOR ROOFTOP UNIT -- NEC 210.63 |