Permit: T06CM05266

Parcel: 11304343A


Addresses:

1050 E NAVAJO RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/02/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/02/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. TIGHTEN ALL LOOSE DEVICES - NEC 406.4
2. LIGHT FIXTURES IN CLOSETS NEED 12" CLEARANCE TO SHELF -- NEC 410.8
3. PROVIDE ARC FAULT PROTECTION FOR SMOKE DETECTORS
NEC 210.12
4. RECEPTACLE FACES TO BE FLUSH WITH COVER PLATE, NO TWISTED OR SETBACK - NEC 406.4D
5. NEED SWITCHED LIGHT OR RECEPTACLE IN LIVING ROOM
NEC 210.70
6. AT WATER HEATER:
A. PROVIDE PROPER DISCONNECTING MEANS - NEC 422.31
(NOT TOGGLE SWITCH)
B. SCREW J-BOX COVER PLATE TO BOX
C. STRAP MC WITHIN 12" OF TERMINATIONS - NEC 330.30
D. IDENTIFY WHITE USED AS HOT - NEC 200.6
7. USE CONNECTOR FOR ROMEX ENTERING HOOD - NEC 334
8. INSTALL DISPOSAL WIRING & COVER FOR ITS RECEPTACLE
9. EAST PORCH LIGHT NOT WORKING
10. AT SERVICE
A. PANEL DIRECTORY NEEDS TO BE CORRECTLY IDENTIFIED IN A CLEAR, PERMANENT, AND LEGIBLE MANNER - NEC 408.4
B. EXPOSE GROUND RODS - NEC 250.53G
C. BOND GAS PIPE - NEC 250.104
D. BURY GROUNDING ELECTRODE CONDUCTOR MINIMUM 12" OR SECURE TO STRUCTURE - NEC 300.5, 250.64
E. MAXIMUM 15 AMPS ON 14GA CONDUCTOR - NEC 310.15
11. PROVIDE SERVICE RECEPTACLE FOR ROOFTOP UNIT --
NEC 210.63