Permit: T06CM05164

Parcel: 127023460


Addresses:

755 N MAGNOLIA AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/21/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/06/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) DUCT SMOKE DETECTORS HAVE BEEN TESTED
2) PROVIDE AIR BALANCE REPORT FOR FINAL
08/05/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PROVIDE AIR BALANCE REPORT
EVERYTHING ELSE IS OK
07/31/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. FINISH DRYER VENT ON ROOF
2. PROVIDE FIRE DAMPER ACCESS DOORS
3. PROVIDE AIR BALANCE REPORT WITH DUCT SMOKE DETECTOR TEST
07/30/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
07/29/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
NO FLEX COPPER ALLOWED ON CONDENSATE DRAINS
BUILD TRAPS PER MANUFACTURERS INSTRUCTIONS
BE SURE ALL UNITS ARE LEVEL
FINISH DRYER VENT ON ROOF
LEFT GAS CARD
NEED DUCT SMOKE DETECTOR TEST
07/28/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*