Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T06CM05164

Parcel: 127023460


Addresses:

755 N MAGNOLIA AV

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
11/06/2007 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
11/05/2007 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PROVIDE UNIFORM SLOPE THROUGHOUT
- IF INSTALLING AT 1% PROVIDE STAMPED LETTER OF APPROVAL FROM ENGINEER
- SUPPORT PIPING, SHADE W/CLEAN FILL
- EXPOSE COUPLINGS COVERED
- OK FOR FOAM WRAPS
10/29/2007 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
09/21/2007 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*