Permit: T06CM05164

Parcel: 127023460


Addresses:

755 N MAGNOLIA AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/21/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/06/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) 2 EM LIGHTS NOT WORKING
2) FINISH POLE LIGHTS
3) FINISH PHOTO CELL AND EXHAUST FAN
4) MARK DISCONNECTS AT SERVICE
5) INSTALL BLANK PLATES
6) REPLACE BAD GFI RECEPTACLES
7) SEAL OPEN KNOCKOUTS/CLOSE OPEN JUNCTION BOXES
8) CHECK WITH BLDG INSPECTOR FOR TCO
08/05/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. STRAP EMT WITHIN 3' OF PANELS
2. NEED PANEL DIRECTORIES
3. OK PANELS
4. MISSING EM LIGHTING. CHECK ALL EM LIGHTS OPERATIONAL
5. COMPLETE ALL PREVIOUS INSPECTIONS
6. FINISH WORK
08/04/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. FINISH INSTALLING PLANS
2. HAVE BAD GFI
3. FINISH INSTALLING DEVICES
4. INSTALL BLANK PLATES
5. HAVE RECEPTACLES WITH NO POWER
6. NEED TO CHECK EM LIGHTS
7. HAVE PANELS OPEN FOR INSPECTION
07/31/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK RECEPTACLE POWE IN ADMIN. RMS. 110, 114, 131, 139
07/30/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
ROOF INSPECTION:
1. INSTALL GFI RECEPT
2. CANNOT USE SJ CORD AS PERMANENT WIRING MEANS IN EXHAUST FANS. NEC 400.7 & 400.8
3. PROPERLY GROUND JUNCTION BOXES @ EXHAUST FANS
CANNOT USE SHEETMETAL SCREWS FOR GROUNDING
07/01/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK TO ENERGIZE "W-3" FOR TESTING