Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/21/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/06/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) 2 EM LIGHTS NOT WORKING 2) FINISH POLE LIGHTS 3) FINISH PHOTO CELL AND EXHAUST FAN 4) MARK DISCONNECTS AT SERVICE 5) INSTALL BLANK PLATES 6) REPLACE BAD GFI RECEPTACLES 7) SEAL OPEN KNOCKOUTS/CLOSE OPEN JUNCTION BOXES 8) CHECK WITH BLDG INSPECTOR FOR TCO |
|
| 08/05/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. STRAP EMT WITHIN 3' OF PANELS 2. NEED PANEL DIRECTORIES 3. OK PANELS 4. MISSING EM LIGHTING. CHECK ALL EM LIGHTS OPERATIONAL 5. COMPLETE ALL PREVIOUS INSPECTIONS 6. FINISH WORK |
|
| 08/04/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH INSTALLING PLANS 2. HAVE BAD GFI 3. FINISH INSTALLING DEVICES 4. INSTALL BLANK PLATES 5. HAVE RECEPTACLES WITH NO POWER 6. NEED TO CHECK EM LIGHTS 7. HAVE PANELS OPEN FOR INSPECTION |
|
| 07/31/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK RECEPTACLE POWE IN ADMIN. RMS. 110, 114, 131, 139 |
|
| 07/30/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ROOF INSPECTION: 1. INSTALL GFI RECEPT 2. CANNOT USE SJ CORD AS PERMANENT WIRING MEANS IN EXHAUST FANS. NEC 400.7 & 400.8 3. PROPERLY GROUND JUNCTION BOXES @ EXHAUST FANS CANNOT USE SHEETMETAL SCREWS FOR GROUNDING |
|
| 07/01/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TO ENERGIZE "W-3" FOR TESTING |