Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2007 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* REPLACED DOUBLE WYE WITH 2 ABS COMBOS OK TO COVER |
|
| 02/02/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) ABS DWV UNDER SLAB OK TO COVER TO EXTERIOR CLEANOUT 2) ABS SEWER OK TO COVER WITH 2 EXCEPTIONS 3) MAY NOT INSTALL DBL WYE IN HORIZONTAL POSITION 4) PROVIDE REDLINE INVERTS FOR BACK WATER VALVE |