Permit: T06CM05079

Parcel: 107141970

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/08/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/16/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ON ROOF
1. SERVICE RECEPTACLE REQUIRED WITHIN 25' AND ON SAME LEVEL AS AC
2. AC DISCONNECT NOT IDENTIFIED, NOT GROUNDED, AND OVER FUSED
3. EMT TO DISCONNECT TO BE RAN SO IT IS NOT A TRIPPING HAZARD/NOT SUBJECT TO PHYSICAL DAMAGE
4. WATER HEATER TO HAVE PROPER J-BOX ACCESS AND LOCK OUT DEVICE
5. GATE MOTOR NOT IN
11/09/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/06/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*