Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/16/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/09/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) OK POWER-CALL FOR FINAL AFTER ENERGIZED 2) RE-IDENTIFY SERVICE EQUIPMENT ASAP |
|
| 08/31/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* THIS INSPECTION MADE 8/10/07? |
|
| 08/10/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS & CEILINGS IN OFFICE AREA |
|
| 05/11/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR SERVICE ONLY: 1) BONDING CONDUCTOR FOR SERVICE MAST'S UNDERSIZED-NEC 250.102C 2) BONDING CONDUCTOR FOR TERM CAN UNDERSIZED-NEC 250.102C 3) BONDING CONDUCTOR TERM CAN TO GUTTER NIPPLE UNDERSIZED-NEC 250.102C 4) ARRANGE BONDING/NEUTRAL CONDUCTORS TO PREVENT OBJECTIONABLE CURRENT-NEC 250.6 (METER BASES TO DISCONNECTS) 5) BONDING CONDUCTORS GUTTER TO METER BASES UNDERSIZED NEC 250.102C 6) GUTTER BONDING CONDUCTOR UNDERSIZED-NEC 250.102C-CHECK ALL BONDING NEC 250 7) SERVICE DISCONNECTS TO BE IDENTIFIED AS SUCH NEC 230.70B 8) DISCONNECTS MOUNTED TO HIGH NEC 404.8A, 230 9) EXPOSE GROUND RODS 10) BOND ALL METAL PIPING TO SERVICE-NEC 250.104 11) GROUNDING ELECTRODE CONDUCTOR TO BE CONNECTED TO NEUTRAL NEC 250.24 AND 250.28 |
|
| 03/08/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS FOR RESTROOM, NO EXH. FANS YET |
|
| 02/09/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CHECK TO MAKE SURE SPACE #'S ARE PER PLAN |