Permit: T06CM05079

Parcel: 107141970

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/16/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/09/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) OK POWER-CALL FOR FINAL AFTER ENERGIZED
2) RE-IDENTIFY SERVICE EQUIPMENT ASAP
08/31/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
THIS INSPECTION MADE 8/10/07?
08/10/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS & CEILINGS IN OFFICE AREA
05/11/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR SERVICE ONLY:
1) BONDING CONDUCTOR FOR SERVICE MAST'S UNDERSIZED-NEC 250.102C
2) BONDING CONDUCTOR FOR TERM CAN UNDERSIZED-NEC 250.102C
3) BONDING CONDUCTOR TERM CAN TO GUTTER NIPPLE UNDERSIZED-NEC 250.102C
4) ARRANGE BONDING/NEUTRAL CONDUCTORS TO PREVENT OBJECTIONABLE CURRENT-NEC 250.6 (METER BASES TO DISCONNECTS)
5) BONDING CONDUCTORS GUTTER TO METER BASES UNDERSIZED NEC 250.102C
6) GUTTER BONDING CONDUCTOR UNDERSIZED-NEC 250.102C-CHECK ALL BONDING NEC 250
7) SERVICE DISCONNECTS TO BE IDENTIFIED AS SUCH NEC 230.70B
8) DISCONNECTS MOUNTED TO HIGH NEC 404.8A, 230
9) EXPOSE GROUND RODS
10) BOND ALL METAL PIPING TO SERVICE-NEC 250.104
11) GROUNDING ELECTRODE CONDUCTOR TO BE CONNECTED TO NEUTRAL NEC 250.24 AND 250.28
03/08/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS FOR RESTROOM, NO EXH. FANS YET
02/09/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CHECK TO MAKE SURE SPACE #'S ARE PER PLAN