Permit: T06CM04879

Parcel: 13416198B


Addresses:

7333 E 22ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
09/11/2008 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
09/10/2008 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
09/09/2008 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. RACEWAYS TO EXTEND NO MORE THAN 3" INTO BOTTOM OF SWITCHGEAR
2. BOND METAL RACEWAYS
3. NEED PROTECTIVE BUSHING FOR WIRES #4 & LARGER
THIS INCLUDES SERVICE CONDUCTORS IN RIC
4. ANCHOR SWITCHGEAR TO PAD PER INSTRUCTIONS
5. PROVIDE LETTER OF TORQUE
6. REMOVE EXCESSIVE ANTI-OXIDATION COMPOUND
7. PROTECT WIRES FROM SHARP EDGES
8. NEED TO POST BOND
09/08/2008 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
08/25/2008 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
OK U.G ALONG NORTH WALL OUTSIDE OF BUILDING