Permit: T06CM04878

Parcel: 134210040


Addresses:

7040 E BROADWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/02/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/01/2007 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
07/26/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- FREEZER CONDENSOR OVERFUSED
- PERMANENTLY I.D ALL EQUIPMENT
- EXTEND ANY SEWER VENT WITHIN 10' OF AIR INTAKES 2' HIGHER
- REDWOOD SLEEPERS MUST SPAN ROOF JOINTS
- FINISH CONNECTING NEW COOLERS
- FINISH INSTALLING GRAVITY AIR VENT & VAPOR HOOD EQUIPMENT.
- PROVIDE REVISED PLANS
- PROVIDE INLINE HEATER
- SECURE ELEC. CONDUITS