Permit: T06CM04878

Parcel: 134210040


Addresses:

7040 E BROADWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
09/28/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
09/26/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
SHALL PROVIDE LADDER FOR ROOF ACCESS
09/21/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELLED
08/02/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
INSTALL REHEAT ON ROOF CALL BACK FOR FINAL
08/01/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
ITEMS #2, #4, #8 FROM 7/27/07 INSPECTION
TO BE COMPLETED WITH 03035 INSPECTION FOR FINAL
07/27/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. APPROVAL OF 03005, 03035, 03036 WAITING ON REVISED APPROVED PLAN WITH REDLINES ON SITE.
2. PROVIDE LONG RADIUS DRAINAGE FITTINGS FOR DISPOSAL DRAINAGE FROM ITEM #4 7/26/07 INSP
3. SUPPORT WATER PIPING FOR 2-COMP & 3-COMP SINK
FROM 7/26/07 ITEM #5
4. WATER HEATER VENTING STILL NOT CORRECT.
FROM ITEM #8 7/26/07
5. WATER HEATER T&P STILL NOT CORRECT
FROM ITEM #9 7/26/07 INSP.
6. WATER HEATER EXPANSION TANK NOT PROPERLY SECURED
ITEM #10 - 7/26/07 INSP
7. OPEN SANITARY DRAIN AT EMPLOYEE RESTROOM & HALLWAY DRAIN VERBAL FROM 7/26/07 INSP
8. INSTALL FILTER DRAIN PER REQUEST ITEM #3 7/26/07 INSP.
07/26/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. CALL IN ALL INSPECTIONS FOR PLUMBING THAT HAVE NOT BEEN APPROVED.
2. SUPPORT ALL WATER & INDIRECT DRAINAGE PIPING AT COOK LINE.
3. PROVIDE 1" AIR GAP AT WATER FILTER DRAIN & TRENCH DRAIN AT ICE MACHINE & SECURE TUBING
4. COMPLETE INSTALLATION OF ALL FIXTURES
(DISPOSAL, GREEN)
5. SUPPORT WATER PIPING AT 2-COMP & 3-COMP SINKS
6. ALL FLOOR SINKS TO HAVE GRATES
7. REPAIR TRENCH DRAIN GRATE TO AVOID TRIPPING HAZARD AT COOK LINE.
8. WATER HEATER TO HAVE CORRECT VENT TERMINATION THRU ROOF TO APPROVED VENT CAP
9. WATER HEATER TEMPERATURE & PRESSURE RELIEF DRAIN SHALL GRAVITY DRAIN TO DAYLIGHT
10. WATER HEATER EXPANSION TANK TO BE SUPPORTED AND SECURED PROPERLY FOR WEIGHT & MOVEMENT.