Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/27/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BLANK OPEN BOXES WHERE LIGHT FIXTURES NOT INSTALLED/ON BACK ORDER 2. INSTALL EXTENSIONS ON BOX MORE THAN 1/4" BACK 3. INSTALL MISSING DEVICE PLATES 4. EM LIGHTS/EXITS NOT OPERATING PROPERLY 5. RECEPTACLE WIRED REVERSED POLARITY 6. DISCONNECT FOR ICE MAKER NEEDS TO BE 6'7" TO CENTER OF HANDLE 7. GROUND ENCLOSURE DISCONNECT FOR DISHWASHER 8. PROPERLY IDENTIFY GROUNDING CONDUCTORS 9. INSTALL APPROVED HANDLE TIES ON SINGLE POLE BREAKERS 10. BREAKER #42 PANEL KP LOOKS BURNED UP. NEEDS TO BE REPLACED 11. INSTALL FILLER PLATES IN PANEL DEAD FRONTS 12. RECEPTACLES AT BACK PREP AREA TO BE GFI 13. INSTALL SERVICE DISCONNECT ON FAN COIL UNIT IN WALK IN FREEZER 14. STRAP SEAL TIGHT WITHIN 12" OF DISCONNECTS 15. APPEARS CONDENSING UNITS ON ROOF MISSING PART OF THE ENCLOSURE. PROVIDE INFORMATION. 16. NEUTRALS CANNOT HAVE OVERCURRENT PROTECTION INSTALLED IN THEM 17. MAKE ALL CONNECTIONS AT DISCONNECTS ROOF TOP 18. SEAL OPEN KNOCKOUTS AT DISCONNECTS ROOF TOP 19. ENSURE ALL ROOF TOP DISCONNECT ENCLOSURES PROPERLY GROUNDED 20. STILL NEED REVISED SET OF PLANS 21. PROTECT CABLES TO PENDANT LIGHTS IN BAR |
|
| 07/26/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. REMOVE ROMEX FROM CEILING 2. SEAL ALL OPEN KNOCKOUTS IN JUNCTION BOXES 3. BLANK OPEN ENDS OF SPARE CONDUITS INTO PANELS 4. SUPPORT JUNCTION BOXES 5. MC CABLE HANGING AT DOORS TO KITCHEN AREA 6. INSTALL ONLY ONE EXTENSION RING ON JUNCTION BOXES 7. OPEN WALL TO INSPECT CONDUIT FOR NEW STAIR LIGHTS OR REMOVE CEMENT TO INSPECT LIGHTS. 8. ELECTRIC IN BAR CEILING NOT FINISHED 9. HAVE ELECTRICAL CONTRACTOR ON SITE FOR FURTHER INSPECTIONS 10. PROPERLY SECURE EMT IN CLOSET BAR AREA 11. NO INSPECTIONS DONE ABOVE TIN CEILING IN BAR 12. ENSURE ALL 2X4 FIXTURES ARE ATTACHED TO CEILING GRID. 13. CANNOT RUN CORDS ABOVE CEILING. INSTALL RECEPTACLES BELOW CEILING. 14. BAR LIGHTING NOT PER PLANS 15. NO PLAN FOR KITCHEN CEILING 16. HAVE APPROVED SET OF DRAWINGS FOR ALL WORK |