Permit: T06CM04878

Parcel: 134210040


Addresses:

7040 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/01/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BLANK OPEN BOXES WHERE LIGHT FIXTURES NOT INSTALLED/ON BACK ORDER
2. INSTALL EXTENSIONS ON BOX MORE THAN 1/4" BACK
3. INSTALL MISSING DEVICE PLATES
4. EM LIGHTS/EXITS NOT OPERATING PROPERLY
5. RECEPTACLE WIRED REVERSED POLARITY
6. DISCONNECT FOR ICE MAKER NEEDS TO BE 6'7" TO CENTER OF HANDLE
7. GROUND ENCLOSURE DISCONNECT FOR DISHWASHER
8. PROPERLY IDENTIFY GROUNDING CONDUCTORS
9. INSTALL APPROVED HANDLE TIES ON SINGLE POLE BREAKERS
10. BREAKER #42 PANEL KP LOOKS BURNED UP. NEEDS TO BE REPLACED
11. INSTALL FILLER PLATES IN PANEL DEAD FRONTS
12. RECEPTACLES AT BACK PREP AREA TO BE GFI
13. INSTALL SERVICE DISCONNECT ON FAN COIL UNIT IN WALK IN FREEZER
14. STRAP SEAL TIGHT WITHIN 12" OF DISCONNECTS
15. APPEARS CONDENSING UNITS ON ROOF MISSING PART OF THE ENCLOSURE. PROVIDE INFORMATION.
16. NEUTRALS CANNOT HAVE OVERCURRENT PROTECTION INSTALLED IN THEM
17. MAKE ALL CONNECTIONS AT DISCONNECTS ROOF TOP
18. SEAL OPEN KNOCKOUTS AT DISCONNECTS ROOF TOP
19. ENSURE ALL ROOF TOP DISCONNECT ENCLOSURES PROPERLY GROUNDED
20. STILL NEED REVISED SET OF PLANS
21. PROTECT CABLES TO PENDANT LIGHTS IN BAR
07/26/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. REMOVE ROMEX FROM CEILING
2. SEAL ALL OPEN KNOCKOUTS IN JUNCTION BOXES
3. BLANK OPEN ENDS OF SPARE CONDUITS INTO PANELS
4. SUPPORT JUNCTION BOXES
5. MC CABLE HANGING AT DOORS TO KITCHEN AREA
6. INSTALL ONLY ONE EXTENSION RING ON JUNCTION BOXES
7. OPEN WALL TO INSPECT CONDUIT FOR NEW STAIR LIGHTS OR REMOVE CEMENT TO INSPECT LIGHTS.
8. ELECTRIC IN BAR CEILING NOT FINISHED
9. HAVE ELECTRICAL CONTRACTOR ON SITE FOR FURTHER INSPECTIONS
10. PROPERLY SECURE EMT IN CLOSET BAR AREA
11. NO INSPECTIONS DONE ABOVE TIN CEILING IN BAR
12. ENSURE ALL 2X4 FIXTURES ARE ATTACHED TO
CEILING GRID.
13. CANNOT RUN CORDS ABOVE CEILING. INSTALL RECEPTACLES BELOW CEILING.
14. BAR LIGHTING NOT PER PLANS
15. NO PLAN FOR KITCHEN CEILING
16. HAVE APPROVED SET OF DRAWINGS FOR ALL WORK