Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/21/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK OUTSIDE WALL AT BAR 2. OK WALL AT MECHANICAL HOOD |
|
| 06/20/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PANELS CANNOT BE SETBACK MORE THAN 1/4" IN NON-COMBUSTIBLE MATERIAL -- NEC 312.3 2. OK BACK WALL UP TO PANELS. DO NOT COVER PANELS 3. NEED UPDATED & APPROVED SET OF DRAWINGS FOR ALL WORK BEING DONE 4. LIGHTING IN CONCRETE STEPS NEVER INSPECTED 5. INSTALL PROPER MUD RINGS ON BAR OUTSIDE WALL 6. OK WALL AT STORAGE AREA IN KITCHEN |
|
| 06/15/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK LOWER "BAR" BOXES 2) VERIFY CAN LIGHTS IN REVERSED POSITION-PLAN NOT REFLECTIVE |
|
| 06/08/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK PVC CONDUIT FLOOR & BACK WALL LOWER BAR *VDV CABELING TO BE AS PER 725.3 & 6, 800.3 & 6 1. PROTECT PVC AT BASE PLATE 2. ADD 02010 TO PERMIT |