Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM04812
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/18/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
09/12/2006 | ELECTRIC - INTERMEDIATE | Denied | 1. HAVE OVERFILLED J-BOXES IN CEILING - CHECK CONDUCTOR FILL AND USE EXTENSION BOX AS REQUIRED -- NEC 314.16 2. USE A GROUND SCREW OR OTHER LISTED METHOD TO GROUND METAL J-BOXES -- NOT A DRYWALL SCREEN NEC 110.3 (ALSO INSTALL K.O BLANKS IN BOXES AS NEEDED) 3. MC IN CEILING TO BE SECURED AND SUPPORTED PROPERLY WITHIN 12" OF TERMINATIONS AND NOT MORE THAN 6' BETWEEN SUPPORTS USE LISTED EQUIPMENT -- NEC 330.30 4. DO A BETTER JOB OF SECURING MC IN WALLS SO IT IS NOT LOOSE -- NEC 110.12 NOTE: SUPPORT WIRES FOR EQUIPMENT IN CEILING MUST BE SEPARATE FROM GRID AND HAVE TWO POINTS OF ATTACHMENT (SECURED @ BOTH ENDS) NEC 300.11 ALSO, MAKE SURE ALL LIGHTING FIXTURES ARE SECURE TO GRID AND HAVE SUPPORT WIRES TO STRUCTURE @ OPPOSITE CORNERS. OK WALL COVER ONLY AFTER WALL CORRECTIONS. |