Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/20/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/10/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED A BUSHING ON WH DISCON. -- WIRING ENTRY AT BACK 2. NIGHT LIGHT AT OFFICE AREA MISSING 3. COMPRESSOR IN WALK IN BACK WALK IN FREEZER, SWITCH NEED SCREW FOR COVER 4. PNL 12A HAS GE 20A CB -- SHOULD BE CH OR BLANK |