Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM04571
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/15/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* 1ST & BASEMENT |
|
02/06/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL KO BLANKS IN CANS AND J-BOXES AS NEEDED-NEC 314.17A 2) INSTALL ALL J-BOX COVERS 3) MC TO BE SECURED WITHIN 12" OF TERMINATIONS-NEC 330.30 C AND PROPERLY SUPPORTED NEC 330.30 4) GRID OR GRID SUPPORT WIRES NOT TO BE BE USED TO SUPPORT ELECTRICAL EQUIPMENT-NEC 300.11 A 5) FINISH ALL WIRING ABOVE CEILING INCLUDING LOW VOLTAGE BEFORE INSPECTION 6) HAVE OVER FILLED J-BOXES NEC 314.16 7) HAVE TO MANY CONDUCTORS UNDER WIRE NUTS NEC 110.313-PROVIDE WIRE NUT FILL INFORMATION 8) INSTALL FUSES IN DISCONNECT 9) REINSPECTION FEE IF NOT CORRECT NEXT INSPECTION 10) 9 FIRE ALARM BOXES TO BE RED-NEC 760 |
|
02/02/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* DO NOT USE CEILING GRID AS SUPPORT FOR CONDUITS OR CABLE |