Permit: T06CM04522

Parcel: 12407179C

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
12/12/2006 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
NEED TO SEE CONDENSATE DRAINS. WILL CHECK ON FINAL.
LEAVE OUT TILES UNDER FAN COILS.
12/04/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
- SUSPENDED ROUGH DUCT OK TO PROCEED
- STRAP ALL FLEX EVERY 5'
- FC-4 NEEDS ACCESS. RELOCATE OSA DUCT & CUT WALL,
RELOCATE ALL THREAD.
- FC-5 RELOCATE AS NEEDED TO PROVIDE ACCESS

STILL NEED TO SEE CONDENSATE DRAINS
PROVIDE SECONDARY DRAINS.