Permit: T06CM04522

Parcel: 12407179C

Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Permit Number - T06CM04522

Inspection Description - ELECTRIC - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
12/29/2006 ELECTRIC - PROGRESS Approved
12/20/2006 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1. INSTALL GFI RECEPTS OVER SINK COUNTERTOP PER PLAN
2. VERIFY DISCONNECTS (SQUARE D) ARE NOT THE FACTORY CALL BACKS.
3. GENERATOR DOOR (WEST) DOES NOT OPEN 90 DEG. DRIVE GROUND RODS FLUSH WITH GRADE.
4. LABEL EM. PANEL & SERVICE DISCONNECT FOR EM. GEN. POSSIBLE BACKFEED.
12/08/2006 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
OK PANEL L1, L2, EPL MAKE UP