Inspection History Details
Permit: T06CM04468
Inspection Status: Not ready for Inspection
Inspection History: OUTDOOR LIGHTING FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2007 | OUTDOOR LIGHTING FINAL | Not ready for Inspection | IVRS - Inspection :* 1) COMPLETE ITEMS 2, 3 & 4 FROM INSPECTION ON 3/6/07 2) CONNECT GROUNDING ELECTRODE CONDUCTOR TO WATER PIPE (COPPER) WITHIN 5' OF ENTERING BLDG 3) NEED REVISION ON WORK TO BE OMITTED 4) OBSERVED 20' OF COPPER WATER PIPE IN GROUND AT RAMADA 5) 2 GROUND RODS INSTALLED FOR SERVICE PEDESTAL OK 6) INSTALL 2 GROUND RODS FOR PANEL AT RAMADA TO SUPTEMENT WATER PIPE |