Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/16/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/04/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE A GROUNDING ELECTRODE SYSTEM AS PER 250 2. CLEAN SURFACE UNDER GROUND BAR 3. BOND SERVICE NIPPLES 4. LABEL BREAKERS 5. LABEL PANEL P-4 PER 690.17 |