Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/08/2009 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 06/05/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : 1. NO PLANS AT SERVICE 2. UFER TO BE STRAPPED TO WALL 3. RISERS TO HAVE LISTED AND APPROVED GUY BACK MAST SUPPORT. 4. BUSHINGS ARE GROUNDED WITH TOO SMALL CONDUCTOR IF DAISY CHAIN METHOD TO BE USED IT WILL EVEN BE LARGER NEUTRAL AT CT CANNOT BE GROUNDED. 5. NO ADDRESS LABEL 6. WATER & GAS BOND? 7. DISCONNECT FOR EXISTING TO BE AT NEW SERVICE LOCATION -- REVIEW ENTIRE SERVICE BEFORE CALLING. |
|
| 05/29/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* |