Permit: T06CM03879

Parcel: 10604024A

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/08/2009 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
06/05/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
1. NO PLANS AT SERVICE
2. UFER TO BE STRAPPED TO WALL
3. RISERS TO HAVE LISTED AND APPROVED GUY BACK MAST SUPPORT.
4. BUSHINGS ARE GROUNDED WITH TOO SMALL CONDUCTOR IF DAISY CHAIN METHOD TO BE USED IT WILL EVEN BE LARGER NEUTRAL AT CT CANNOT BE GROUNDED.
5. NO ADDRESS LABEL
6. WATER & GAS BOND?
7. DISCONNECT FOR EXISTING TO BE AT NEW SERVICE LOCATION -- REVIEW ENTIRE SERVICE BEFORE CALLING.
05/29/2007 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*