Permit: T06CM03829

Parcel: 13623007Y

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM03829

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/27/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
OK FOR FINAL
03/23/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
GAS IS ON FOR BOILER INSPECTION ONLY AT BOILERS
DIELECTRIC PROTECTION FOR WATER PIPING OK
CERTIFICATION TO TUCSON WATER OK
NOTES FROM 3/9/07 ARE APPROVED
STEAM & CONDENSATE PIPING PER PLAN 100 PSI TEST OK

SEE NOTES FROM 3/15/07 AND PROVIDE INSULATION ON STEAM & CONDENSATE PIPING
03/19/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
COMPLETE ALL WORK REQUIRED BY APPROVED PLAN AND NOTES LEFT ON SITE.
03/15/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
SUPPORT PIPING CORRECTLY, PROVIDE INSULATION & HEAT TRAPS PER PLAN & 2003 ECC FOR WATER HEATER.
EXPOSE WATER HAMMER DEVICES.
MAKE ALL FIXTURES WATER TIGHT.
STEAM & CONDENSATE 100 PSI TEST OK FOR INSULATION ON HEADER PIPING. TEST UP TO INDIVIDUAL SHUT OFF VALVES AT EACH PIECE OF EQUIPMENT. PROVIDE LISTINGS FOR VALVES USED FOR STEAM & CONDENSATE.
03/09/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE DIELECTRIC PROTECTION FOR WATER PIPING COPPER TO STEEL.
2. COMPLETE ALL WORK
3. PROVIDE CERTIFICATIONS

NOT COMPLETE LIST

ALL EQUIPMENT SHALL BE INSTALLED PER APPROVED PLAN
SHALL REQUIRE STATE BUILDING INSPECTION