Permit: T06CM03829

Parcel: 13623007Y

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM03829

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/19/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/15/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) SUPPORT FLEX DROPS TO CONTROL UNIT FOR BOILERS
2) PANEL B NEED CLEARANCE IN FRONT OF IT AND DOWN TO GRADE OUT 36"
3) CORRECT SERVICE LABELING FOR B
03/09/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BATHROOM SW NEEDS COVER
2. FIXTURES IN BACK ROOM ARE OF A LISTED TYPE TO BE IN T-BAR CEILING NOT LISTED FOR OPEN HANG.
3. UNION DRY CLEANING MACHINE, LABEL DISCONNECT & SUPPORT TRANSITION OF EMT TO FLEX, CANNOT BE LEFT LOOSE. DRY CLEANING MACHINE CALLS FOR 70 AMPS MIN, #6 WIRE TO IT FROM SW #6 ONLY 65 AMPS.
4. SECURE POWER POLES OUT IN FRONT AREA
5. IMPROPER CLEARANCE FOR DISCONNECTS IN COMPRESSOR ROOM
6. DISCON. FOR MARVEL DRYER TO BE IDENTIFIED, HAVE IMPROPER TRANSFER OF WIRING FROM SW TO WALL AND ID WIRES WITH PROPER COLOR CODES
7. SEAL HOLES IN BOILER & SCRAP OFF BEHIND GRDS
8. PNL A NO SCHEDULE -- MAKE SURE IT LOOKS LIKE PLAN
9. PNL B NO SCHEDULE -- MAKE SURE IT LOOKS LIKE PLAN
10. VERIFY WORKING EM LIGHTS
HAVE ELECT REVIEW JOB PRIOR TO RECALL