Permit: T06CM03784

Parcel: 14027040C


Addresses:

2660 E BILBY RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/21/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/19/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
RECEIVED LETTERS FROM ARCH. FOR INFO ON BOOTH,
HOWEVER, BOOTH STILL REQUIRES EVAL. AS PER LAST INSP. NOTES
06/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
DENIED PER NEC 2002 110.2, 3
NO LISTING OR LABELING BY CERTIFIED OSHA LABORATORY

INFORMATION ON SITE - INSTRUCTIONS FOR THE CROSS FLOW POWER COAT BOOTH STATE ON PAGE 5 THAT THE UNIT IS NOT LABELED BY AN OSHA CERTIFIED TESTING LAB - ONLY COMPONENTS DOES HOWEVER, SAY ETL CERTIFICATION IS AVAILABLE
THIS DEPARTMENT IS REQUIRING THIS CERTIFICATION
CONTRACTOR IS NOT RESPONSIBLE FOR THIS
INSTALLER & PROVIDER ARE
THIS IS REQUIRED FOR A FINAL
06/21/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
NOTE THAT PLANS DO NOT SPECIFY OTHER THAN "SPRAY BOOTH" FOR POWDER COTE BOOTH - THIS APPLICATION FALLS UNDER ART.516 OF THE NEC
CONTR. SAYS THERE WILL BE NO FLAMMABLE LIQUIDS OR POWDER TO BE APPLIED IN BOOTH.

PLEASE HAVE ARCH. OF RECORD TO CLASSIFY "SPRAY BOOTH" OR NOT AS INSTALLED BOOTH DOES NOT MEET THE REQUIREMENTS OF ART. 516 NEC