Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/19/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/15/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE SEE REQUIREMENTS FOR SHOWER VALVE LOCATION IN 36" X 36" TRANSFER SHOWER. VALVE SHALL BE 38"-48" ABOVE FINISHED FLOOR DIRECTLY OPPOSITE SEAT PAGE 57, 58, 59 2003 AMERICAN NATIONAL STANDARD ICC ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES BOOK. 2. INSTALL CLOSET FLANGE FOR INSPECTION PER INSTALLATION STANDARD #5 2003 UPC PRIOR TO SETTING STOOL. |
|
| 03/05/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WATER TEST WASTE & VENT THRU ROOF OK WATER PIPING OK 1. SHALL SEE FINAL INSTALL OF H/C SHOWER WITH SHOWER VALVE INSTALL PROPERLY SUPPORTED. 2. SUPPORT 3" VENT OVERHEAD IN RESTROOM |