Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/10/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/14/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RECEPTACLE IN LIGHT FIXTURE IN BATHROOM NOT GFI PROTECTED NEC 210.8 2) MARK ACCESSORIES FOR A/C UNIT IF NON MARK NON 3) CANNOT SEE FUSE SIZING MARK ON FUSES FOR AIR HANDLER 4) INSTALL DISCONNECT FOR WATER HEATER NEC 422.31 5) OUTSIDE LIGHT NOT PER PLAN |
|
| 05/29/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CALL FOR FINAL ONCE ENERGIZED |
|
| 05/24/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |