Permit: T06CM03227

Parcel: 120076460


Addresses:

505 W AJO WY

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/21/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
02/20/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. CONDENSATE CANNOT TERMINATE ONTO THE PARKING LOT.
2. VENT ON CONDENSATE DRAIN MUST BE DOWNSTREAM OF THE TRAP.
3. ADD MORE ANTI-SLIP STRIPS ON ROOF.
02/08/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE SCREWS IN T-TOPS
2) PAINT EXPOSED PVC WITH LATEX PAINT
3) PROVIDE MINIMUM 1/8" PER FT SLOPE
4) PROVIDE SERVICE PLATFORMS AROUND UNITS