Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/21/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 02/20/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. CONDENSATE CANNOT TERMINATE ONTO THE PARKING LOT. 2. VENT ON CONDENSATE DRAIN MUST BE DOWNSTREAM OF THE TRAP. 3. ADD MORE ANTI-SLIP STRIPS ON ROOF. |
|