Permit: T06CM03227

Parcel: 120076460


Addresses:

505 W AJO WY

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
10/09/2006 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
IN COMPLIANCE WITH APPROVED PLANS
REAR WALL DETAIL 4 ON SHEET S2
10/03/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
PROVIDED REPORT
09/25/2006 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/19/2006 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
- GROUTED WITHOUT INSPECTION
- HIGH BOND BEAMS, REAR WALL AND 2 SIDE WALLS
- ACI GUIDELINES FOR HIGH LIFT GROUT NOT FOLLOWED (CLEANOUTS, ETC)
- RETURN TO STRUCTURAL ENGINEER FOR REPAIRS AND RECOMMENDATIONS ON HOW TO PROCEED WITH INSPECTION.
PACOMETER, G-BR, X-RAY, ETC.