Permit: T06CM03085

Parcel: 10602262A


Addresses:

3602 N ORACLE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM03085

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/05/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/28/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
FIX PNL B SCHEDULE
01/26/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
HAVE ELECTRICIAN ON SITE FOR INSPECTION
CLEAR ACCESS AROUND PANELS, RECEPTACLES FOR INSPECTION
01/10/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. DISCONNECTS FOR EQUIPMENT ON ROOFTOP ARE NOT PROPERLY IDENTIFIED AS TO PANEL AND CKT.
2. PANEL DIRECTORYS ARE NOT PROPERLY IDENTIFIED -
NEC 408.4
3. FLEX ON ROOF NOT PROPERLY SECURED/SUPPORTED AND USE PROPER STRAPS, NOT TIE STRAPS - NEC 350.30
4. NEED TO SEAL THE INTERIOR NOT AROUND (OUTSIDE) OF ALL RACEWAYS ENTERING COOLERS AND USE PROPER SCREWS FOR BOX COVERS, NOT DRYWALL SCREWS -
NEC 300.7 HAVE ALL THESE OPEN FOR INSPECTION.

NOTE: MAKE SURE ALL LOADS ORIGINATE FROM PANELS AS OUTLINED ON PLANS.
12/13/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
PROVIDE LADDER ACCESS FOR ROOF
08/18/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) OK ABOVE FEEDERS
2) SEAL PENETRATIONS INTO COOLERS DUCT SEAL OK
3) LABEL DISCONNECTS ON ROOF FOR UNIT NUMBER
4) SUPPORT SEAL TIGHT ON ROOF
5) REJECT PINS IN NEW 200 AMP DISCONNECT
6) COUNTERS NOT INSPECTED YET, NOR COFFEE BAR