Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM03085
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/05/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
02/28/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* FIX PNL B SCHEDULE |
|
01/26/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* HAVE ELECTRICIAN ON SITE FOR INSPECTION CLEAR ACCESS AROUND PANELS, RECEPTACLES FOR INSPECTION |
|
01/10/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DISCONNECTS FOR EQUIPMENT ON ROOFTOP ARE NOT PROPERLY IDENTIFIED AS TO PANEL AND CKT. 2. PANEL DIRECTORYS ARE NOT PROPERLY IDENTIFIED - NEC 408.4 3. FLEX ON ROOF NOT PROPERLY SECURED/SUPPORTED AND USE PROPER STRAPS, NOT TIE STRAPS - NEC 350.30 4. NEED TO SEAL THE INTERIOR NOT AROUND (OUTSIDE) OF ALL RACEWAYS ENTERING COOLERS AND USE PROPER SCREWS FOR BOX COVERS, NOT DRYWALL SCREWS - NEC 300.7 HAVE ALL THESE OPEN FOR INSPECTION. NOTE: MAKE SURE ALL LOADS ORIGINATE FROM PANELS AS OUTLINED ON PLANS. |
|
12/13/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* PROVIDE LADDER ACCESS FOR ROOF |
|
08/18/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) OK ABOVE FEEDERS 2) SEAL PENETRATIONS INTO COOLERS DUCT SEAL OK 3) LABEL DISCONNECTS ON ROOF FOR UNIT NUMBER 4) SUPPORT SEAL TIGHT ON ROOF 5) REJECT PINS IN NEW 200 AMP DISCONNECT 6) COUNTERS NOT INSPECTED YET, NOR COFFEE BAR |