Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING 2ND FLOOR WILL CHECK RELOCATED FAN COIL 1ST FLOOR ON FINAL |
|
| 07/17/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* REPAIR CONDENSATE DRAIN. SECURE DIFFUSERS. DIFFUSERS NOT INSTALLED PER DETAIL ON PLANS. PROVIDE A LETTER OF ACCEPTANCE FROM ENGINEER. |
|
| 06/19/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* IECC CHAPTER 8 REQUIRES MIN. R5 DUCT INSULATION WHAT STANDARD ARE YOU USING TO ALLOW R4.2 PROVIDE LETTER FROM ENGINEER. OK FOR CEILING TILES. LEAVE OUT AROUND EACH FAN COIL 1ST FLOOR INSPECTION ONLY. |