Permit: T06CM03066

Parcel: 13405116F


Addresses:

994 S HARRISON RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T06CM03066

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/18/2007 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR CEILING 2ND FLOOR
WILL CHECK RELOCATED FAN COIL 1ST FLOOR ON FINAL
07/17/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
REPAIR CONDENSATE DRAIN.
SECURE DIFFUSERS.
DIFFUSERS NOT INSTALLED PER DETAIL ON PLANS.
PROVIDE A LETTER OF ACCEPTANCE FROM ENGINEER.
06/19/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
IECC CHAPTER 8 REQUIRES MIN. R5 DUCT INSULATION
WHAT STANDARD ARE YOU USING TO ALLOW R4.2
PROVIDE LETTER FROM ENGINEER. OK FOR CEILING TILES.
LEAVE OUT AROUND EACH FAN COIL 1ST FLOOR INSPECTION ONLY.